+49 40 890 616 0 info@mueller-gastechnik.de

Medium pressure regulator 070

Medium pressure regulator 071

Medium pressure regulator 070 / 071

Classification​
Container systems commercial & industrial

Medium pressure regulators – PN 16
Mg: 24 kg/h – Pd: 0.8 to 4.0 bar

DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG

The pressure regulators type 070 and 071 are single-stage regulators with a hose connection on one side, which offer a wide range of applications. The regulators can be integrated into all systems that require a regulated pressure.

They can regulate an inlet pressure of up to 16 bar to a nominal pressure of 0.8 up to 4.0 bar.

Type 070 has a fixed outlet pressure and type 071 an adjustable outlet pressure, both regulators are delivered without OPSO and PRV.

TECHNICAL DATA
  • DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG
  • Capacity: 24 kg/h (propane)
  • Inlet pressure: 1.8 – 16 bar
  • Outlet pressure: 0.8 – 4 bar
  • Inlet connection: G 1/2 “IG or others on request
  • Outlet connection: hose connection or others on request
  • Weight: 1 kg
  • Gas: LPG / LNG / propane / butane / natural gas or others on request
  • Operating temperature: -40°C to +50°C
OPERATING PRINCIPLES

The pressure regulators type 070 and 071 are single-stage regulators that offer a wide range of applications. The regulators can be integrated into all systems that require a regulated pressure.

They can regulate an inlet pressure of up to 16 bar to a nominal pressure of up to 4 bar.

PRODUCT TYPES
Medium pressure regulator MDR-070 Outlet pressure Capacity Order Number
(Fixed adjustable outlet pressure)
MDR-070 G 1/2 IG x SLA 0,8 bis 4,0 bar 24 kg/h 9 09 070H0017
Medium pressure regulator MDR-071 Outlet pressure Capacity Order Number
(Fixed adjustable outlet pressure)
MDR-071-G 1/2 IG x SLA – adjustable 0,8 bis 4,0 bar 24 kg/h 9 09 071H0017

 

INSTALLATION AND OPERATING INSTRUCTIONS

Medium pressure regulators – PN 16
Mg: 24 kg/h – Pd: 0.8 to 4.0 bar

DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG

TYP MDR-070 / 071 without OPSO and PRV

DESCRIPTION
The medium pressure regulators 070/071 consist of a 1st stage regulator which reduces the unregulated pressure from the LPG tank to a fixed outlet pressure and keeps it constant. An overpressure safety relief valve (PRV) is fitted as optional safety equipment.

A. INDIVIDUAL DESCRIPTIONS
1. Pressure regulator
The pressure regulator reduces the unregulated pressure from the LPG tank to a fixed outlet pressure.

B. MODE OF OPERATION
The pressure regulator reduces the unregulated pressure from the LPG tank to a nominal 0.8 to 4.0 bar in a single stage.

CAUTION! All activities described in points C, D and E may only be carried out by authorised specialist personnel.

C. ASSEMBLY
The pressure regulator is connected to the extraction valve of the liquid gas container with the POL connection according to DIN 4811-2, whereby it is to be supported on the container by means of the support device supplied.
It is essential to ensure that the pressure regulator is installed with an inclination of approx. 20° so that the ventilation openings point downwards (see note on the medium pressure regulator).

IMPORTANT! • Only use proper tools for assembly. • Prevent sealants from getting into the gas-carrying components. • Always counteract threaded connections with suitable spanners. • After assembly, a careful leak test must be carried out.

D. START-UP
Commissioning is carried out by slowly opening the tapping valve on the liquid gas tank.