HAGZ-40-„t“

This house connection is an indoor system “t” for liquid gas according to model 4b DIN 4811, in which the 2nd stage regulator, the gas meter and the fittings of the house entrance are mounted on a mounting plate inside the building. A blow-off line must be led from the ventilation opening of the 2nd stage regulator to the outside.

The upstream pressure regulator is a 1st stage regulator according to model 3a, 4a or 5a DIN 4811 with a nominal outlet pressure of 0.75 bar.

Indoor system “t” with gas meter (mounted on mounting plate)
House connection – “t” – model 4b DIN 4811

PN 4 low-pressure regulator – “f” – 24 kg/h
DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG

Technical Data of the upstream MDR 310
  • DVGW approved: According to EN 16129/ CE approved according to 2016/426/EC
  • Inlet pressure: 1.75-16 bar
  • Inlet connection: Pole or others on request
  • Outlet connection: G 1/2 “IG or others on request
  • Capacity: 40 kg/h (propane)
  • Outlet pressure: 0.75 bar or other on request
  • Overpressure safety shut-off valve (OPSO):2.2 bar or other on request
  • Overpressure safety relief valve (PRV):2.5 bar or another on request
  • Weight: 2 kg
  • Gas: LPG/LNG/Propane/Butane/Natural gas or other on request
  • Operating temperature: -40°C to +80°C
Technical Data of the low pressure regulator NDR 320
  • DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG
  • Inlet pressure: 0.5-4 bar
  • Inlet connection: G 1/2 “IG or others on request
  • Outlet connection: G1/2 “IG or others on request
  • Capacity: 24 kg/h (propane)
  • Outlet pressure: 50 mbar or other on request
  • Overpressure safety shut-off valve (OPSO): 95-132 mbar
  • Overpressure safety relief valve (PRV): 135-150 mbar
  • Weight: 2 kg
  • Gas: LPG/LNG/Propane/Butane/Natural gas or others on request
  • Operating temperature: -40°C to +80°C
FEATURES
  • incl. TAE
  • incl. insulating piece
  • incl. test connection on the inlet and outlet side
  • incl. shut-off valves on the inlet and outlet side
  • incl. low-pressure regulator type: NDR-320 with 90° outlet
  • incl. gas meter with mounting plate
  • incl. mounting material
  • mounted on a hot-dip galvanised mounting plate MP-1 (H/W: 460 x 460 mm)
  • optionally available with gas flow monitor GS
PRODUCT TYPES

 

Description  Inlet Outlet Emergency supply Oder number
HAGZ-40-T-LVS15 LVS 15 LVS 15 nein 1 00 034 9 3 115 5
HAGZ-40-T-LVS18 LVS 18 LVS 18 nein 1 00 034 9 3 118 5
HAGZ-40-T-LVS22 LVS 22 LVS 22 nein 1 00 034 9 3 122 5
HAGZ-40-T-RVS15 RVS 15 RVS 15 nein 1 00 034 9 3 215 5
HAGZ-40-T-RVS18 RVS 18 RVS 18 nein 1 00 034 9 3 218 5
HAGZ-40-T-RVS22 RVS 22 RVS 22 nein 1 00 034 9 3 222 5
HAGZ-40-T-PVS15 PVS 15 PVS 15 nein 1 00 034 9 3 515 5
HAGZ-40-T-PVS18 PVS 18 PVS 18 nein 1 00 034 9 3 518 5
HAGZ-40-T-PVS22 PVS 22 PVS 22 nein 1 00 034 9 3 522 5

All controller stations and house connection stations are also available with integrated flow monitor. Please add 16 for GS1.6, 25 for GS2.5 or 40 for GS4 to the order number. The gross prices are increased accordingly by the gross price of the flow monitor.