Automatic changeover valve 056
Large cylinder systems according to F2
The automatic changeover valve can operate 2 gas cylinders at the same time, this regulates the inlet pressure of the cylinder to the correspondingly set outlet pressure.
The advantage of this changeover valve is that a cylinder change is possible without interrupting operation.
DVGW approved: According to EN 16129/ CE approved according to 2016/426/EG
TECHNICAL DATA
- DVGW approval: according to EN 16129 / CE marking according to 2016/426/EC.
- Inlet connection: M18x1.25 female, G3/8 LH female, G3/8 RH female or others on request.
- Outlet connection: G1/4, G3/8, G1/2, G3/4 or others on request
- Weight: Weight approx. 1.6 kg
- Gas: LPG / LNG / propane / butane / natural gas or others on request
- Operating temperature: -40°C to +50°C
- 056-1 (Green lever)
Inlet pressure: 1.4-12 bar
Operating pressure: 0.9 bar
Reserve pressure: 0,4 bar
Capacity: 4 kg/h - 056-2 (Orange lever)
Inlet pressure: 2-12 bar
Operating pressure: 1.6 bar
Reserve pressure: 1.0 bar
Capacity: 6 kg/h - 056-3 (Black lever)
Inlet pressure: 2.4-12 bar
Operating pressure: 2 bar
Reserve pressure: 1.4 bar
Capacity: 12 kg/h - 056-4 (Red lever)
Inlet pressure: 2.8-12 bar
Operating pressure: 2.5 bar
Reserve pressure: 1.8 bar
Capacity: 12 kg/h
OPERATING PRINCIPLES
The automatic changeover valve can operate 2 gas cylinders simultaneously. One cylinder is the working cylinder, which is used until the pressure in the working cylinder drops below a defined pressure.
Now the reserve cylinder is used. You must switch the knob to reserve, this then becomes the working cylinder. You can now change the empty cylinder during operation. This has the advantage of providing you with a constant gas supply.
PRODUCT TYPES
Automatic changeover valve 056 | Operating pressure | Performance | Order Number | |
Automatic changeover valve 056-1 GFA x GFA | 0.9 bar | 4 Kg/h | 1 00 056H0100 | |
Automatic changeover valve 056-2 GFA x GFA | 1.6 bar | 6 Kg/h | 1 00 056H0200 | |
Automatic changeover valve 056-3 GFA x GFA | 2.0 bar | 12 Kg/h | 1 00 056H0300 | |
Automatic changeover valve 056-4 GFA x GFA | 2.5 bar | 12 Kg/h | 1 00 056H0400 | |
Automatic changeover valve 056 | Operating pressure | Performance | Order Number | |
(for systems with 4 cylinders and more) | ||||
Automatic changeover valve 056-1 for 4 cylinders and more | 0.9 bar | 4 Kg/h | upon request | |
Automatic changeover valve 056-2 for 4 cylinders and more | 1.6 bar | 6 Kg/h | upon request | |
Automatic changeover valve 056-3 for 4 cylinders and more | 2.0 bar | 12 Kg/h | upon request | |
Automatic changeover valve 056-4 for 4 cylinders and more | 2.5 bar | 12 Kg/h | upon request | |
Connection set for multi-cylinder systems for 4 cylinders and more (per connection) | 9 09 089P0060 | |||
Hose connection M20x1,5 x W21,8 LH (per connection) | 9 09 089H0010 |